uPxxR -gb

PID Controller for reducing substances, solfites, metabisulphites, SO2 etc.

uP-IP

PID controller for reducing substances Mod.uPxxR

Microprocessor based PID controller, fully programmable, suitable for panel mounting (IP54 protection degree) and outdoor installation (IP65 housing). Instrument configuration is easily performed via display and keyboard and calibration is automatic.
Measure and temperature are indicated on a 5 digit red LED display.
The electronic unit supplies to the polarization voltage  requred to make it selective to the specific reducing  substance to be measured.
Mod.uPxxR can be directly connected to the sensor of sulphites, metabisulphites, sulphur anydride and to   the pertinent temperature sensing element.
The measure is compensated for temperature variations, according to dedicated algorithms specific for each parameter and  displayed in engineering units.  Temperature compensated value is used in the PID algorithm.  The PID controller is available either with analogic control output  (4-20 mA or 0-10V, galvanically isolated) or with digital control output (conatct output); in this versione the 4-20 mA (or 0-10 V) output is available for temperature compensated  measure retransmission.
The instrument provides 4 digital outputs that can be configured as NC or NO via software and can be programmed as low alarm, high alarm, alarm with hysteresis or windows alarm.
The 4 digital outputs are from relays. If the control output is from relay R1 is used for control action.
Two digital inputs are available, for digital hold of the measure, and for the connection to an external flowswitch  (output freezing in absence of sample flow into the cell). The instrument is optionally available with cleaning sequence included: in this version it can drive the chemical cleaning of the sensor through a specific algorithm, with programmable timers, driving the detergent pump through R4 relay.
Measuring ranges are:  0-2000 ppb;  0-10 ppm;  10-2000 ppm
In the version with contact output control action the analog output can be freely associated to any interval  inside the measuring range.
Power supply: 24 Vdc, 24 Vac, 115 Vac, 230 Vac,  ±10%, 50/60 Hz, max.consumption: 3.3 VA

These selective cells are used for the measure and control of many reducing substances, such as metabisulphites (or metabisulfites, S2O5=), sulphur dioxide and sulphites (or sulfites, SO3=)  in various applications, as in fruit juice processing, in wine (oenology), in IV range products processing, in fruit and vegetables disinfection and processing,  in textile industry, in tanneries, in drinking water plants