701C -gb
AISI 316 SS Through flow cell c/w chemical cleaning system Mod.701C4A0A0
AISI 316 SS Through flow cell c/w chemical cleaning system Mod.701C4A0A0
Through flow cell for the measure of turbidity, Mod.702D and Mod.702E
Turbidity sensor for direct installation in closed pipelines, Mod.701H and Mod.701G
PID controller for turbidity control Mod.uPxxR
Microprocessor based PID controller, fully programmable, suitable for panel mounting (IP54 protection degree) and outdoor installation (IP65 housing). Instrument configuration is easily performed via display and keyboard and calibration is automatic.
Measure and temperature are indicated on a 5 digit red LED display.
Mod.uP can be directly connected to the turbidity sensor; the measure is displayed in engineering units. Measured value is used in the PID algorithm. The PID controller is available either with analogic control output (4-20 mA or 0-10V, galvanically isolated) or with digital control output (conatct output); in this versione the 4-20 mA (or 0-10 V) output is available for temperature compensated measure retransmission.
The instrument provides 4 digital outputs that can be configured as NC or NO via software and can be programmed as low alarm, high alarm, alarm with hysteresis or windows alarm.
The 4 digital outputs are from relays. If the control output is from relay R1 is used for control action.
Two digital inputs are available, one for digital hold of the measure, and one for the input of an external alarm (e.g. level switch, temperature switch etc.)
The instrument is optionally available with cleaning sequence included: in this version it can drive the chemical cleaning of the sensor through a specific algorithm, with programmable timers, driving the detergent pump through R4 relay.
Measuring ranges are 0.0-2.0 NTU; 0.0-20.0 NTU; 0.0-200.0 NTU; 0.0-2000.0 NTU
In the version with contact output control action the analog output can be freely associated to any interval inside the measuring range.
Power supply: 24 Vdc, 24 Vac, 115 Vac, 230 Vac, ±10%, 50/60 Hz, max.consumption: 3.3 VA
Immersion probe for the measure of turbidity, Mod.702A and Mod.702B